search

PIV12,5-275/4+0, Hakel PIV12,5-275/4+0, chống sét lan truyền, thiết bị chống sét lan truyền nguồn điện 3 pha Hakel, chống sét

0 ₫
Thuế

PIV12,5-275/4+0, Hakel PIV12,5-275/4+0, chống sét lan truyền, thiết bị chống sét lan truyền nguồn điện 3 pha Hakel, chống sét

Số lượng

PIV12,5-275/4+0, Hakel PIV12,5-275/4+0, chống sét lan truyền, thiết bị chống sét lan truyền nguồn điện 3 pha Hakel, chống sét

 

PIV12,5-275/4+0

PIV12,5-275/4+0

PIV12,5-275/4+0 is a four-pole lightning and surge arrester Type 1+2 according to EN 61643-11 and IEC 61643-11. These arresters are recommended for use in the Lightning Protection Zones Concept at the boundaries of LPZ 0 – 1 (according to IEC 1312-1 and EN 62305), where they provide the equipotential bonding and discharge of both, the lightning current and the switching surge, which are generated in power supply systems entering the building. The use of the lightning current arresters PIV12,5-275/4+0 is mainly in the power supply lines, which are operated as TN-S system. The main use of PIV12,5-275/4+0 arrester is in structures of LPL III – IV according to EN 62305 ed.2.

The marking of DS specifies a version with remote monitoring.

Internal wiring diagram
Internal wiring diagram
Dimension drawing
Dimension drawing
Installation diagram
Installation diagram
PARAMETERS
Test class according to EN 61643-11 ed. 2 and IEC 61643-11   TYP 1+2, CLASS I+II
Network type   TN-S
Maximum continuous operating voltage UC 275 V AC / 350 V DC
Maximum discharge current Imax 50 kA
Impulse discharge current for class I test (10/350) L/N limp 12,5 kA
Charge Q 6,25 As
Specific energy for class I test W/R 39 kJ/Ω
Total discharge current (10/350) L1+L2+L3+N->PE Itotal 50 kA
Total discharge current (8/20) L1+L2+L3+N->PE Itotal 200 kA
Nominal discharge current for class II test (8/20) In 25 kA
Voltage protection level Up < 1,2 kV
Temporary overvoltage (TOV) UT 335 V/5 s
Response time tA < 25 ns
Max. back-up fuse   160 A gL/gG
Short-circuit withstand capability 160 A gL/gG ISCCR 60 kArms
LPZ   0-1
Housing material   Polyamid PA6, UL 94 V-0
Degree of protection of enclosure   IP20
Operating temperature   -40°C ... +80 °C
Cross-section of the connected conductors (at tightening moment of clamps 3 Nm)   25 mm2 (solid)
16 mm2 (wire)
Method of assembly   DIN rail 35 mm
Failure signalisation (S)   pushed in - ok / pushed out - failure
Lifetime   min. 100 000 h
Weight m 560 g
Article number   10 195
 
CERTIFICATIONS
DOWNLOADS
Catalogue

Tham Chiếu Cụ Thể