search

DSH TT 2P 255, DSH TT 2P 255 941 110, 941 110, 941110, phân phối độc quyền thiết bị chống sét 1 pha DEHN, DEHNshield TT 2P

0 ₫
Thuế

DSH TT 2P 255, DSH TT 2P 255 941 110, 941 110, 941110, phân phối độc quyền thiết bị chống sét 1 pha DEHN, DEHNshield TT 2P

Số lượng

DSH TT 2P 255, DSH TT 2P 255 941 110, 941 110, 941110, phân phối độc quyền thiết bị chống sét 1 pha DEHN, DEHNshield TT 2P

 

Download tài liệu DSH TT 2P 255

Download tài liệu hướng dẫn lắp đặt DSH TT 2P 255

Download tài liệu thiết bị chống sét DEHN

 

  • Application-optimised and prewired spark-gap-based type 1 and type 2 combined lightning current and surge arrester
  • Compact design due to space-saving spark gap technology with a width of only 1 module / pole
  • Fulfils the minimum requirements on the lightning current discharge capacity according to IEC 60364-5-53
  • Allows compact lightning equipotential bonding including protection of terminal equipment
  • Discharge capacity up to 50 kA (10/350 µs)
  • Operating state / fault indication by green / red indicator flag in the inspection window
  • High follow current extinguishing capacity (Ifi = 25 kArms)
 

Application-optimised and prewired combined lightning current and surge arrester for single-phase TT and TN systems with a nominal voltage of 230 V (1+1 configuration).

 

Application-optimised two-pole combined arrester for 230/400 V TT systems SPD type 1 + type 2 in accordance with EN 61643-11 For use in compact and simply equipped electrical installations with reduced technical requirements Spark gap technology with follow current limitation Operating state/fault indication by indicator flag in the inspection window Leakage-current-free, non-exhausting design Max. continuous operating voltage: 255 V a.c. Voltage protection level: <= 1.5 kV Lightning impulse current (10/350): 25 kA Energy coordinated in accordance with IEC 62305-4 (VDE 0185-305-4) with type 2 and 3 arresters of the Red/Line family, as well as directly coordinated with terminal equipment DIN rail mounted device in accordance with DIN 43880, 2 modules
 
delivery and installation.
 
Brand: DEHN + SÖHNE
Type: DSH TT 2P 255
Part No.: 941 110
 
or equivalent.
 

Type

DSH TT 2P 255

Part No.

941 110

SPD according to EN 61643-11 / IEC 61643-11

type 1 + type 2 / class I + class II

Energy coordination with terminal equipment (≤ 5 m)

type 1 + type 2 + type 3

Nominal voltage (a.c.) (UN)

230 V (50 / 60 Hz)

Max. continuous operating voltage (a.c.) (UC)

255 V (50 / 60 Hz)

Lightning impulse current (10/350 µs) [L+N-PE] (Itotal)

25 kA

Specific energy [L+N-PE] (W/R)

156.25 kJ/ohms

Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp)

12.5 / 25 kA

Specific energy [L-N]/[N-PE] (W/R)

39.06 / 156.25 kJ/ohms

Nominal discharge current (8/20 µs) [L-N]/[N-PE] (In)

12.5 / 25 kA

Voltage protection level [L-N]/[N-PE] (UP)

≤ 1.5 / ≤ 1.5 kV

Follow current extinguishing capability [L-N]/[N-PE] (Ifi)

25 kArms / 100 Arms

Follow current limitation / Selectivity

no tripping of a 32 A gG fuse up to 25 kArms (prosp.)

Response time (tA)

≤ 100 ns

Max. mains-side overcurrent protection

160 A gG

Temporary overvoltage (TOV) [L-N] (UT) – Characteristic

440 V / 120 min. – withstand

Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic

1200 V / 200 ms – withstand

Operating temperature range (TU)

-40 °C ... +80 °C

Operating state / fault indication

green / red

Number of ports

1

Cross-sectional area (L, N, PE, 9) (min.)

1.5 mm2 solid / flexible

Cross-sectional area (L, N, PE, 9) (max.)

35 mm2 stranded / 25 mm2 flexible

For mounting on

35 mm DIN rails acc. to EN 60715

Enclosure material

thermoplastic, red, UL 94 V-0

Place of installation

indoor installation

Degree of protection

IP 20

Capacity

2 module(s), DIN 43880

Approvals

KEMA, VDE, UL

Extended technical data:

---------------------------------

Voltage protection level [L-PE] (UP)

2.0 kV

Weight

275 g

GTIN

4013364137899

PU

1 pc(s)

Part No.

941 110

Tham Chiếu Cụ Thể