TYPE 1 AC SURGE PROTECTOR : DS250VG

DS250VG series Type 1+2+3 surge protector VG Technology

 

DS254VG-120/G

- Type 1+2+3 unipolar surge protector
- 25 kA on 10/350µs impulse
- Low voltage Up
- Internal disconnection, status indicator and remote signaling
- Optimized to TOV
- IEC 61643-11 compliance
- UL1449 ed.4 recognition

The DS250VG is an extreme duty Type 1+2+3 AC surge protector device designed to protect at the entrance of the electrical installation.
This SPD is particularly useful in a high lightning density area where the risk of heavy surge current or even direct strike is high (eg: buildings equipped with lightning rods).
The DS250VG is one-pole SPD and can be used in common mode or common and differential mode.
DS250VG AC surge protectors are designed to be connected in multi-pole configuration to protect single-phase, 3-phase and 3-phase+Neutral AC networks, sometimes associated with a dedicated N/PE SPD.

Citel model : DS254VG-120/G

Part Number : 2757

Click on the blocks to display detailed characteristics

Electrical characteristics
Hide details
SPD type
follow test IEC 61643-11
  1+2+3
Network
  120/208 V 3-phase+N
AC system
  TT-TNS
Nominal line voltage
Un
120 Vac
Max. AC operating voltage L-N
Uc
150 Vac
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
without disconnection
UT
180 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn
without disconnection or with safety disconnection
UT
230 Vac withstand
Temporary Over Voltage N/PE (TOV HT)
without disconnection or with safety disconnection
UT
1200 V/300A/200 ms withstand
Operating current
LeakAge current at Uc
Ic
none
Follow current
If
none
Nominal discharge current
15 x 8/20 µs impulses
In
30 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax
70 kA
Impulse current by pole
max. withstand 10/350µs by pole
Iimp
25 kA
Total lightning current
max. total withstand @ 10/350 µs
Itotal
100 kA
Withstand on Combinaison waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc
6 kV
Withstand on overvoltages IEEE C62.41.1
  20 kV
Admissible short-circuit current
Isccr
50000A
Max. load current
IL
100 A
Connection mode
  L/N and N/PE
Protection mode(s)
  MC/MD
Protection level
@In (8/20µs) between L/PE
Up L/PE
1.5 kV
Residual voltage
@ In - 8/20µs waveform
Up-in
0.7 kV
Specific energy by pole
max. withstand 10/350 µs
W/R
156 kJ/ohm
Protection level L/PE
Up L/PE
-
Protection level L/N
for multipolar surge protector
Up L/N
1 kV
Mechanical characteristics
Hide details
Technology
  VG
SPD configuration
  3-phase+Neutral
Connection to Network
  By screw terminals : 6-35 mm² / by bus
Format
  1-pole modular box assembled
Mounting
  Symmetrical rail 35 mm (EN60715)
Housing material
  Thermoplastic UL94-V0
Operating temperature
  -40/+85°C
Protection rating
  IP20
Outdoor application
  N
Failsafe behavior
  Disconnection
Disconnection indicator
  1 mechanical indicator by pole
Remote signaling of disconnection
  output on changeover contact
Associated disconnection devices
Hide details
Thermal disconnector
  internal
Installation ground fault breaker
  Type `S` or delayed
Fuses
  Fuses type gG - 315 A
Standards compliance
Hide details
Standards compliance IEC 61643-11 / EN 61643-11 / UL1449 4ed.
Certification EAC