DG YPV SCI 600 FM, DG YPV SCI 600 FM 950 536, 950 536, 950536, chống sét hệ thống quang 600 V, chống sét lan truyền

New product

DG YPV SCI 600 FM, DG YPV SCI 600 FM 950 536, 950 536, 950536, chống sét hệ thống quang 600 V, chống sét lan truyền

DG YPV SCI 600 FM, DG YPV SCI 600 FM 950 536, 950 536, 950536, chống sét hệ thống quang 600 V, chống sét lan truyền

 

Download tài liệu DG YPV SCI 600 FM

Download tài liệu lắp đặt DG YPV SCI 600 FM

 

Download tài liệu thiết bị chống sét DEHN

 

 

 

Multipole DEHNguard compact YPV SCI 600 FM surge arrester
Multipole arrester for use in photovoltaic systems up to 600 V d.c.
with three-step d.c. switching device, width: 3 modules
with remote signalling contact
Type 2 SPD according to EN 50539-11
For use in accordance with IEC 60364-7-712
Safe electrical isolation in the protection module
Max. PV voltage: <= 600 V d.c.
Total discharge current: 40 kA
Voltage protection level: <= 2.5 kV
Short-circuit current rating Iscpv: 1000 A
Fault indication
Mehrpoliger Photovoltaik-Ableiter bis 600 V DC
mit 3-stufiger DC-Schalteinrichtung, Breite 3TE
Mit Fernmeldekontakt
Typ 2 nach EN 50539-11
Einsetzbar gemäß IEC 60364-7-712
Sichere elektrische Trennung verhindert
Brandschäden infolge DC-Schaltlichtbögen
Maximale PV-Spannung: <= 600 V dc
Gesamtableitstoßstrom: 40 kA
Schutzpegel: <= 2,5 kV
Kurzschlussfestigkeit Iscpv: 1000 A
Defektanzeige

delivery and installation.

Brand: DEHN + SÖHNE
Type: DG YPV SCI 600 FM
Part No.: 950 536

or equivalent.


 

Type

DG YPV SCI 600 FM

Part No.

950 536

SPD according to EN 50539-11

type 2

Max. PV voltage (UCPV)

600 V

Short-circuit current rating (ISCPV)

1000 A

Total discharge current (8/20 µs) (Itotal)

40 kA

Nominal discharge current (8/20 µs) [(DC+/DC-) --> PE] (In)

12.5 kA

Max. discharge current (8/20 µs) [(DC+/DC-) --> PE] (Imax)

25 kA

Voltage protection level (UP)

≤ 2.5 kV

Voltage protection level at 5 kA (UP)

≤ 2 kV

Response time (tA)

≤ 25 ns

Operating temperature range (TU)

-40 °C ... +80 °C

Operating state / fault indication

green / red

Number of ports

1

Cross-sectional area (min.)

1.5 mm2 solid / flexible

Cross-sectional area (max.)

35 mm2 stranded / 25 mm2 flexible

For mounting on

35 mm DIN rails acc. to EN 60715

Enclosure material

thermoplastic, red, UL 94 V-0

Place of installation

indoor installation

Degree of protection

IP 20

Capacity

3 mod(s)., DIN 43880

Approvals

KEMA, UL

Type of remote signalling contact

changeover contact

Switching capacity (a.c.)

250 V / 0.5 A

Switching capacity (d.c.)

250 V / 0.1 A, 125 V / 0.2 A, 75 V / 0.5 A

Cross-sectional area for remote signalling terminals

max. 1.5 mm2 solid / flexible

Weight

285 g

GTIN

4013364154995

PU

1 pc(s)

Part No.

950 536