Coordinated DEHNbloc Maxi NH00 255 lightning current arrester
Coordinated single-pole lightning current arrester
in NH 00 design with high follow current limitation
Type 1 SPD according to EN 61643-11
RADAX Flow spark gap technology
for follow current limitation
Max. continuous operating voltage: 255 V a.c.
Voltage protection level: <= 2.5 kV
Lightning impulse current (10/350): 25 kA
Follow current extinguishing capability: up to 100 kArms
Energy-coordinated with arresters of the
Red/Line series according to IEC 62305-4

delivery and installation.

Brand: DEHN + SÖHNE
Type: DBM NH00 255
Part No.: 900 255

or equivalent.


 

Type

DBM NH00 255

Part No.

900 255

SPD according to EN 61643-11 / IEC 61643-11

type 1 / class I

Nominal voltage (a.c.) (UN)

230 V (50 / 60 Hz)

Max. continuous operating voltage (a.c.) (UC)

255 V (50 / 60 Hz)

Lightning impulse current (10/350 µs) (Iimp)

25 kA

Specific energy (W/R)

156.25 kJ/ohms

Voltage protection level (UP)

≤ 2.5 kV

Follow current extinguishing capability (a.c.) (Ifi)

50 kArms

Follow current limitation / Selectivity

no tripping of a 32 A gG fuse up to 50 kArms (prosp.)

Response time (tA)

≤ 100 ns

Max. backup fuse (L) up to I= 50 kArms

315 A gG

Temporary overvoltage (TOV) (UT) – Characteristic

440 V / 120 min. – withstand

Operating temperature range (parallel connection) (TUP)

-40 °C ... +80 °C

Number of ports

1

For mounting on

NH fuse holders of size NH00

Enclosure material

thermoplastic, red, UL 94 V-0

Place of installation

indoor installation

Degree of protection

according to installation situation

Extended technical data:

Use in switchgear installations with prospective short-circuit currents of more than 50 kArms (tested by the German VDE)

– Max. prospective short-circuit current

100 kArms (220 kApeak)

– Limitation / Extinction of mains follow currents

up to 100 kArms (220 kApeak)

– Max. backup fuse (L) up to IK = 100 kArms

315 A gG

Weight

194 g

GTIN

4013364125773

PU

1 pc(s)

Part No.

900 255